APPLICATION
The single core power cable are designed for distribution of electrical power with nominal voltage Uo/U ranging from 3.8/6.6KV to 19/33KV and
frequency 50Hz. They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in
water as well as for installation on cable trays for industries, switchboards and power stations.
STANDARD
BS 6622
BS 7835 (LSZH)
CONSTRUCTION
Conductor:Plain annealed copper or aluminum complying with IEC 60228/BS 6360. Copper conductors shall be stranded (class 2) and
aluminum conductors shall be either solid or stranded (class 2).
Conductor Screen: Extruded layer of semi-conducting cross linkable compound is applied over the conductor and shall cover the surface
completely. The minimum thickness is 0.3mm and the maximum resistivity shall not exceed 500 Ohm-m at 90°C.
Insulation: Insulation is of cross-linked polyethylene compound XLPE (GP8) conforming to BS 7655-1.3 or EPR (GP7), conforming to
BS 7655-1.2.